Google Cloud London Outage Caused by Backup Power Configuration Error
A misconfigured power sensor caused a six-hour London cloud outage by failing to trigger backup generators, leading to widespread service disruption.

A six-hour service disruption in the London cloud region on October 20 was caused by a programmable logic controller (PLC) misconfiguration that prevented emergency generators from activating. The failure originated in the europe-west2-b availability zone following an external utility cable fault. During a scheduled maintenance period, the facility was operating on a single-feed configuration. The PLC, responsible for triggering backup power, was to monitor voltage on the utility side of an isolated circuit breaker rather than the building's internal power feed. Consequently, the controller detected residual voltage on the isolated line and failed to issue a start command to the generators when the primary feed collapsed.
As the facility’s uninterruptible power supply (UPS) batteries were designed only for short-term bridging, they depleted within minutes, resulting in a total power loss for the data hall. The outage triggered an automated failover process that redirected workloads to the remaining two availability zones in the London region. This sudden surge in traffic saturated capacity, causing secondary performance degradation, elevated latency, and API timeouts across the broader region. More than 35 core services, including compute, storage, and database platforms, were affected.
The incident impacted a wide range of institutional clients, including major financial services, judicial systems, and logistics providers. The scale of the disruption has prompted inquiries from regulators regarding concentration risk and the resilience of critical infrastructure hosted on third-party cloud platforms. In response, the provider has reconfigured the PLC logic to verify both undervoltage conditions and physical breaker positions, ensuring that generator activation is no longer dependent on a single sensing point. Future risk mitigation strategies will focus on enhancing the robustness of failover protocols during maintenance windows to prevent similar cascading regional impacts.
More stories
- Europe faces attribution gap after 16 cyber, physical incidents
- PIF backs Grand Theft Auto as Saudi players embrace game
- Signal limits screenshots to curb AI access to messages
- Cognition runs Devin Mac workspaces on EC2 in 6 AWS regions
- Salesforce engineers cut 600-failure triage to 90 minutes
- Türkiye Desk: GTA 6 puts console access and network demand in focus
- FURSOY posts 500 MHz Linux-capable RISC-V core
- SpaceX catches Starship upper stage but loses its booster
- The Signal: Google defends Play Store fees in £1bn UK case
- China builds new data center capacity as cheap power comes online
Latest news
- Trump prepares tariffs on China and other major exporters
- New-car buyers pay record average $50,087 in October
- Banks face ECB reserve debate over liquidity and profits
- Investors see Anthropic debut gains fade below $83 a share
- Iraq orders federal control over Kurdish-area oilfields
- Germans oppose Ukraine aid as poll shows support slipping
- Kim Jong-un receives 10 envoys after constitutional shift
- Ukraine claims Libya strike sinks Russian naval corvette